Permit Information
Permit NumberFIR05-00400
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1116 S VISTA AVE
Project NameSPR OH VISTA VILLAGE PHASE I
Customer Number 
ePlanReview 
Description
VISTA VILLAGE SHOPPING CENTER (BUILDING "E" SHELL ONLY) * To install a complete overhead fire sprinkler system in a new 6,135-ft/2, single story retail multi-tenant shell building with a 800-ft/2 covered entry facade across the front. This building is fully fire sprinklered. Separate permits required for any T.I. work. Underground fire service supply is permitted separately under FIR05-00315 by the same contractor. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-000423.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/17/20061/17/20061/18/2006PPASS
DetailsForrest France
c/n items are complete, plan items requiring resubmittal have been addressed with the TI submittals. Inspection passed.
INSP-Final Inspection1/9/20061/10/20061/10/2006PFAIL
DetailsForrest France
Need to test alarms when complete, provide calc. sticker, pressure relief valve, main drain sign, perform forward flow, backflow certification, "911 sign" at bell, complete items on c/n. Overhead hydro test passed inspection at this time.
INSP-Sprinkler Rough-in/Hydro9/14/20059/15/20059/15/2005AFAIL
DetailsForrest France
Bushings are not allowed in this application at the fittings on the north side grid main see NFPA 13 6.4.6.1, provide seismic clearance for the 2" and 3" mains where they pass through the masonry wall, upright heads at the south attic are over 15' apart, inspectors test orfice is not correctly sized, provide approved plans at next inspection, provide relief valve for gridded system at riser.