INSP-Final Inspection | 2/16/2010 | 2/16/2010 | 2/16/2010 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit okay for final- required alarm work finished via project related FIR07-00116.
|
INSP-Final Inspection | 1/17/2006 | 1/17/2006 | 1/18/2006 | P | NR |
Forrest France
|
|
|
Per contractor not ready for final inspection. The control valves for the antifreeze system must be monitored by the fire alarm panel, connection will require a FA permit.
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in for antifreeze system at front canopy is acceptable to cover.
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of antifreeze system at front canopy is satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 7/26/2005 | 7/26/2005 | 7/26/2005 | P | FAIL |
Forrest France
|
|
|
Pendent heads along storefront canopy do not meet OH2 spacing requirements dictated by this occupant type and use for this specific area (see review notes- re-submittals req. for any changes), EQ attatchments in wood truss members must be through bolted, attic heads along sloped ceilings must orient deflector with the slope, perform hydrostatic test when system is complete and changes have been made.
|