INSP-Final Inspection | 12/6/2005 | 12/6/2005 | 12/6/2005 | P | PASS |
Forrest France
|
|
|
All c/n items are complete, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 10/26/2005 | 10/26/2005 | 10/26/2005 | P | FAIL |
Forrest France
|
|
|
One head at sauna room is blocked by an adjacent cabinet, no escutcheons are installed at this time, discussed head location in laundry room and kitchen.
|
INSP-Sprinkler Rough-in | 7/29/2005 | 7/29/2005 | 7/29/2005 | P | PART |
Forrest France
|
|
|
Overhead fire sprinkler rough-in is satisfactory. Final pending installation of escutcheons, SW verification below catwalk, spare heads in headbox, verify current annual inspection on system.
|
INSP-Sprinkler Rough-in | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | FAIL |
Forrest France
|
|
|
Minimum spacing requirements for the installed residential heads in storage room 103, bathroom closet 207, and master bedroom 201 are not met as required, (see plan review note #17).
|