Permit Information
Permit NumberFIR05-00422
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 245 S CAPITOL BLVD Unit: 1607
Project NameSPR TZO-NAH RESIDENCE
Customer Number 
ePlanReview 
Description
(TZO-NAH - GROVE HOTEL CONDOS - SUITE 1607) To remove all existing sprinklers with and replacing with new fire sprinklers, while relocating 7 and adding 2. This building is fire sprinklered because it is a high-rise. This area is residential and requires a minimum .1 (light hazard occupancy) density. The fire sprinkler work is related to some new interior walls and the combining two dwelling units, each having 1 level, to create one 3,907 square foot, for a 2 level dwelling unit, located on the 16th and 17th floors of the Grove Hotel building. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00422.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/6/200512/6/200512/6/2005PPASS
DetailsForrest France
All c/n items are complete, fire sprinkler permit finaled.
INSP-Sprinkler Rough-in10/26/200510/26/200510/26/2005PFAIL
DetailsForrest France
One head at sauna room is blocked by an adjacent cabinet, no escutcheons are installed at this time, discussed head location in laundry room and kitchen.
INSP-Sprinkler Rough-in7/29/20057/29/20057/29/2005PPART
DetailsForrest France
Overhead fire sprinkler rough-in is satisfactory. Final pending installation of escutcheons, SW verification below catwalk, spare heads in headbox, verify current annual inspection on system.
INSP-Sprinkler Rough-in7/28/20057/28/20057/28/2005PFAIL
DetailsForrest France
Minimum spacing requirements for the installed residential heads in storage room 103, bathroom closet 207, and master bedroom 201 are not met as required, (see plan review note #17).