Permit Information
Permit NumberFIR05-00424
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7447 W EMERALD ST
Project NameSPR UG-THE JEWEL
Customer Number 
ePlanReview 
Description
THE JEWEL (RETAIL SHELL) - To install approximately 208'-0" of 6" C-900 PVC, form a tap in the north east parking lot south of Cole, running south, around the east side of the building and west into a fire sprinkler riser room located on the south central side of the proposed structure, up through the floor approximately 6" with a transition fitting and blank flange. This fire service supply is for the fire protection in a new 11,940-ft/2, one story, wood framed, retail shell building. Separate permit required for the overhead shell system. This fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00424.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/12/20065/12/20065/12/2006PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Supply line flush9/20/20059/21/20059/21/2005APART
DetailsForrest France
UG fire supply line flush is satisfactory.
INSP-Supply line flush8/30/20058/30/20058/31/2005PPART
DetailsForrest France
This inspection was for an underground hydro test which passed.
INSP-Supply line flush7/22/20057/22/20057/22/2005PPART
DetailsTroy Cobbley
Inspection was for cover. Underground piping is ok to cover