Permit Information
Permit NumberFIR05-00428
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 909 E RESERVE ST
Project NameSPR MARQUIS CARE
Customer Number 
ePlanReview 
Description
MARQUIS CARE AT SHAW MOUNTAIN * This permit is associated with establishing a certificate of occupancy for the entire facility. To add, relocate and remove fire sprinklers for the minor interior and exterior remodel of an existing nursing home. Fire sprinkler work is related to upgrades to the east wing corridor to create smoke partition walls & 1-hour roof/ceiling assembly in corridor for type V-A construction per sec. 407, 2003 IBC; modification of select doors, relocate the 2-hour fire wall to location shown between east and main wing, with 4'-0" foot lower roof assembly a minimum of 1-hour roof ceiling construction on each side of 2-hour wall instead of parapet w/o openings in roof; create a new nurse station / office from patient room (#1); combine two patient rooms (#65 & # 67) to make new lounge / soft room, restroom (#65a) converted to storage; convert patient room (#45) to weight room; and install mock-up kitchen in dining / living room (#110). NOTE: BLD02-00194 for T.I. is still in effect with remodel still in progress. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00428.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/10/20063/10/20063/10/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/9/20063/10/20063/10/2006APART
DetailsForrest France
All areas inspected are satisfactory, final pending replacement of one painted head in the restroom (see enlarged detail E for location), and installation of missing escutcheons at the restroom and office area at the end of the NE wing.
INSP-Final Inspection3/8/20063/9/20063/9/2006PDEFR
DetailsForrest France
No time for this inspection today, to be rescheduled per conversation with contractor for 3/10 in the am.
INSP-Final Inspection3/3/20063/6/20063/6/2006ANR
DetailsForrest France
Per phone conversation with Brad of TVFP the project is not ready for inspection at this time.
INSP-Sprinkler Rough-in9/29/20059/30/20059/30/2005APART
DetailsForrest France
Relocated heads in storage room 132, EQ bracing in corridor, and head at north entry vestibule are acceptable.
INSP-Sprinkler Rough-in8/11/20058/11/20058/12/2005PPART
DetailsTroy Cobbley
Sprinkler rough-in as shown on the city plans is ok. Pendant head at north entry into large room needs to match existing. Earth quake bracing is lacking in the north end. Per the approved plans, Design Hazard/Limitiations, this permit shall meet the minimum requirements of the International FIre Code. The entire sprinkler system shall meet the code requirements under which it was installed and if it doesn't it must be brought up to current code. This is for all aspects of the sprinkler system including but not limited to hangers, EQ bracing and sprinkler spacing.