Permit Information
Permit NumberFIR05-00459
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 760 W BROAD ST
Project NameEDWARDS THEATRE BODO 7
Customer Number 
ePlanReview 
Description
The shell and core fire alarm permit (FIR05-00076) must be finaled prior to occupancy for this fire alarm permit. This permit is to provide HVAC shutdown, fire/smoke damper control, total notification (speaker/strobes) to an existing fire alarm system. A new NAC extender panel will be installed in the Data Room (32) on the 3rd floor. The required manual fire alarm system includes HVAC shutdown, fire/smoke damper control, door release and notification throughout (voice/evac).

4/18/2006 - Plan Modification consists of the as-built conditions. Actual EOL locations, wattage settings and speaker/strobe locations.

The associated building permit (BLD 05-00922) is to construct a 56,493 square foot multi-theater complex (2,407 square foot 1st story, 45,536 square foot 2nd story, 8,550 square foot 2nd story mezzanine) within an existing 138,293 square foot building. Work is to include 2-hr fire barrier walls, interior nonbearing walls, open stairways, 2-hr enclosed stairways, 2 public restrooms accessible to the disabled, 1 unisex restroom accessible to the disabled, 1 employee restroom accessible to the disabled, 1-hr exit passageways, elevated floors, suspended ceilings, millwork, and finishes. All work shall comply with the approved drawings, the plan review report, and applicable codes. The fire sprinkler system shall comply with 2002 NFPA 13 as regulated by the Fire Department. **CJW** EDWARDS THEATRES 9 SCREEN CINEMA - BODO BLDG #7 - This building is fire sprinklered for fire area and for the multi-theater complex.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/25/200610/27/200610/27/2006APASS
DetailsForrest France
Updated plans have been provided reflecting actual locations of EOL's as requested, voltage drop and EOL locations field verified, final inspection passed, permit finaled.
INSP-Final Inspection10/5/200610/9/200610/9/2006ACANC
DetailsForrest France
Cancel per contractor due to access issues.
INSP-Final Inspection5/15/20065/16/20065/16/2006AFAIL
DetailsForrest France
Spot checked EOL locations do not match plans.
INSP-Final Inspection2/27/20062/28/20062/28/2006PFAIL
DetailsForrest France
Need to provide plan resubmittals for field review of changes as requested by previous inspection.
INSP-Final Inspection11/10/200511/10/200511/10/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanniman's permission until resubmittals and elevator are finished and finaled. Elevator is not to be used until inspected.
INSP-Alarm Testing11/9/200511/9/200511/10/2005PDONE
DetailsTroy Cobbley
Tested duct detectors, 2 EOL VD, Cinemedia, verified amperage on the two amplifiers, reverified db levels in the projection areas (changed because of over amperage of one amplifier). Resubmittals are required.
INSP-Alarm Testing11/8/200511/8/200511/8/2005ACANC
DetailsForrest France
Air flow test for duct detectors is incorrect, measurements were derived from the supply not the return as required.
INSP-Alarm Testing11/2/200511/3/200511/4/2005PFAIL
DetailsForrest France
Tested theatres, need to retest two EOL , add speaker in theatre 3, still need to test and verify correct locations for duct detectors, see correction notice for listing of remaining items, final inspection not approved at this time.
INSP-Alarm Testing11/1/200511/1/200511/1/2005PFAIL
DetailsForrest France
Decible levels are inconsistent with requirements for theatre areas.
INSP-Alarm Testing10/30/200510/31/200510/31/2005AFAIL
DetailsForrest France
Remove NAC A1:3 and speaker circut A1:3, revise duct detectors, NAC B4 circut is less than 21.6 EOL, verify wall mounted AV's are not blocked by video games when installed, check battery backup quantity allowed at theatres, partial inspection only no theatres inspected at this time.
INSP-Alarm Testing10/24/200510/25/200510/25/2005PFAIL
DetailsForrest France
The duct detectors are installed on the supply side, not return as code requires.
INSP-Alarm Testing10/24/200510/24/200510/24/2005PCANC
DetailsForrest France
No time available for this inspection today.
INSP-Alarm Testing10/20/200510/21/200510/21/2005ANR
DetailsForrest France
The core and shell permit must be finaled prior to TI approval.
INSP-Alarm Testing10/18/200510/20/200510/20/2005ANR
DetailsForrest France
Work is not complete per discussion with contractor, inspection to be rescheduled.
INSP-Final Inspection10/13/200510/14/200510/14/2005ACANC
DetailsForrest France
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie brian anderson cancl