INSP-Final Inspection | 10/25/2006 | 10/27/2006 | 10/27/2006 | A | PASS |
Forrest France
|
|
|
Updated plans have been provided reflecting actual locations of EOL's as requested, voltage drop and EOL locations field verified, final inspection passed, permit finaled.
|
INSP-Final Inspection | 10/5/2006 | 10/9/2006 | 10/9/2006 | A | CANC |
Forrest France
|
|
|
Cancel per contractor due to access issues.
|
INSP-Final Inspection | 5/15/2006 | 5/16/2006 | 5/16/2006 | A | FAIL |
Forrest France
|
|
|
Spot checked EOL locations do not match plans.
|
INSP-Final Inspection | 2/27/2006 | 2/28/2006 | 2/28/2006 | P | FAIL |
Forrest France
|
|
|
Need to provide plan resubmittals for field review of changes as requested by previous inspection.
|
INSP-Final Inspection | 11/10/2005 | 11/10/2005 | 11/10/2005 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Dave Hanniman's permission until resubmittals and elevator are finished and finaled. Elevator is not to be used until inspected.
|
INSP-Alarm Testing | 11/9/2005 | 11/9/2005 | 11/10/2005 | P | DONE |
Troy Cobbley
|
|
|
Tested duct detectors, 2 EOL VD, Cinemedia, verified amperage on the two amplifiers, reverified db levels in the projection areas (changed because of over amperage of one amplifier). Resubmittals are required.
|
INSP-Alarm Testing | 11/8/2005 | 11/8/2005 | 11/8/2005 | A | CANC |
Forrest France
|
|
|
Air flow test for duct detectors is incorrect, measurements were derived from the supply not the return as required.
|
INSP-Alarm Testing | 11/2/2005 | 11/3/2005 | 11/4/2005 | P | FAIL |
Forrest France
|
|
|
Tested theatres, need to retest two EOL , add speaker in theatre 3, still need to test and verify correct locations for duct detectors, see correction notice for listing of remaining items, final inspection not approved at this time.
|
INSP-Alarm Testing | 11/1/2005 | 11/1/2005 | 11/1/2005 | P | FAIL |
Forrest France
|
|
|
Decible levels are inconsistent with requirements for theatre areas.
|
INSP-Alarm Testing | 10/30/2005 | 10/31/2005 | 10/31/2005 | A | FAIL |
Forrest France
|
|
|
Remove NAC A1:3 and speaker circut A1:3, revise duct detectors, NAC B4 circut is less than 21.6 EOL, verify wall mounted AV's are not blocked by video games when installed, check battery backup quantity allowed at theatres, partial inspection only no theatres inspected at this time.
|
INSP-Alarm Testing | 10/24/2005 | 10/25/2005 | 10/25/2005 | P | FAIL |
Forrest France
|
|
|
The duct detectors are installed on the supply side, not return as code requires.
|
INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 | P | CANC |
Forrest France
|
|
|
No time available for this inspection today.
|
INSP-Alarm Testing | 10/20/2005 | 10/21/2005 | 10/21/2005 | A | NR |
Forrest France
|
|
|
The core and shell permit must be finaled prior to TI approval.
|
INSP-Alarm Testing | 10/18/2005 | 10/20/2005 | 10/20/2005 | A | NR |
Forrest France
|
|
|
Work is not complete per discussion with contractor, inspection to be rescheduled.
|
INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 | A | CANC |
Forrest France
|
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie brian anderson cancl
|