INSP-Final Inspection | 4/18/2008 | 4/18/2008 | 4/18/2008 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled, see site inspection comments 10/20/05.
|
INSP-Sprinkler Rough-in/Hydro | 10/19/2005 | 10/20/2005 | 10/20/2005 | P | PASS |
Forrest France
|
|
|
This inspection was for a final on the alarm permit which passed.
|
INSP-Final Inspection | 10/18/2005 | 10/19/2005 | 10/19/2005 | P | FAIL |
Forrest France
|
|
|
The manual pull station has not yet been replaced, the zoning has not been corrected, a lock at the FACP breaker has not been installed, inspection does not allow for time to amend these items while waiting on site, inspection to be rescheduled for 10/20 p.m.
|
INSP-Final Inspection | 9/22/2005 | 9/23/2005 | 9/23/2005 | P | FAIL |
Forrest France
|
|
|
The pull station installed does not match submittals and is mounted too high, provide lock at breaker to FACP, two smoke alarms are installed on a different zone than approved plans show, restroom smoke alarms report as office smoke zone 1, provide resubmittals reflecting correct zoning, phone lines, battery, smoke at panel, restroom smoke tested okay, no other items tested at this time.
|