INSP-Final Inspection | 10/5/2005 | 10/7/2005 | 10/7/2005 | A | PASS |
Forrest France
|
|
|
Items on correction notice have been completed, fire alarm finaled.
|
INSP-Final Inspection | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | FAIL |
Forrest France
|
|
|
Outside bells at both risers failed to function, duct smoke detectors tested okay, need record of signal verification at next inspection, still need sd cut sheet.
|
INSP-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 | P | FAIL |
Forrest France
|
|
|
Provide cut sheet for smoke detector at FACP to determine wall mounted listing, provide sign at door to FACP room, zone 18 and 19 tampers report as waterflow, provide updated map with matching addressing at panel, verify lock and label at breaker to FACP, need sprinkler contractor to facilitate testing of flow switches, pump run, phase reversal etc., still need to test four duct smoke detectors, no access provided at this inspection.
|