Permit Information
Permit NumberFIR05-00528
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6710 SUPPLY WAY
Project NameSPR WESTERN TRAILER SHOP
Customer Number 
ePlanReview 
Description
WESTERN TRAILERS * To install a 4" wet, Ordinary Hazard Group 2 Occupancy overhead fire sprinkler system in a new 22,300-ft/2, (w/1000-ft/2 mezzanine), one story, pre-engineered "Butler" steel shop building. The main level includes a 16,000 square foot shop, a 4,015-ft/2 machine shop and 1000-ft/2 foot office area. The mezzanine has office space and a mechanical room. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply is permitted under FIR05-00265. This permit is attached to building permit: BLD05-00672.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/200512/5/200512/5/2005APASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Sprinkler Rough-in/Hydro12/2/200512/5/200512/5/2005APASS
DetailsForrest France
Resubmittals have been reviewed and verified, c/n items are complete, fire sprinkler permit finaled.
INSP-Final Inspection11/14/200511/14/200511/14/2005PPART
DetailsForrest France
Approval pending resubmittals reflecting the required changes.
INSP-Final Inspection11/9/200511/10/200511/10/2005AFAIL
DetailsTroy Cobbley
Resubmittals not approved yet. No inspection performed.
INSP-Final Inspection11/2/200511/2/200511/2/2005PFAIL
DetailsForrest France
Provide resubmittals reflecting items 1 thru 9 on plan review notes, attatched outside mechanical room is not shown on plans, missing longitudinal brace on 21/2 " main, need 200 degree head in upstairs mech room and janitors room 1st floor, install relief valve at riser, need 911 sign, install head cage at SW in mech room, not all items reviewed at this time.
INSP-Final Inspection10/28/200510/31/200510/31/2005APART
DetailsForrest France
Overhead hydrostatic test passed inspection.
INSP-Supply line flush10/17/200510/18/200510/18/2005APART
DetailsForrest France
Underground fire supply line flush is satisfactory.