Permit NumberFIR05-00556
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 962 S ALLANTE PL
Project NameSPR PROSOURCE CARPET WRHSE
Customer Number 
ePlanReview 
Description
PROSOURCE WHOLESALE CARPET & WAREHOUSE - To install an Extra Hazard Group 1 Occupancy wet pipe fire sprinkler system in a 4,040-ft/2 portion of a new 14,000-ft/2 single story, concrete tilt-up exterior wall, Type III-B (Type III-B building required for lack of fire flows) mercantile building. This fire sprinkler will only be installed in the high piled combustible storage area meeting IFC Chapter 23 requirements. All fire sprinkler work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-01065.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/1/200511/1/200511/1/2005PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/27/200510/28/200510/28/2005AFAIL
DetailsTroy Cobbley
Left message on Jims phone. No body at job site.
INSP-Final Inspection10/27/200510/27/200510/27/2005PFAIL
DetailsTroy Cobbley
backflow preventor surges, provide additional heads for the spare head box, provide test papers, provide verification that the heads can remain.
INSP-Sprinkler Rough-in/Hydro9/26/20059/27/20059/27/2005APART
DetailsTroy Cobbley
Underground hydro passed. Sprinkler rough-in passed except that the wrong upright sprinkler heads have beem installed. If heads remain resubmittals will be required and the overhead hydro will be passed. If the heads are changed out to the VK200's as per plan then the hydro needs redone.