INSP-Final Inspection | 2/15/2006 | 2/17/2006 | 2/17/2006 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 2/14/2006 | 2/15/2006 | 2/15/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need to forward flush the backflow preventor and install one additional hanger at the front entrance.
|
INSP-Final Inspection | 2/1/2006 | 2/2/2006 | 2/2/2006 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide review comments. Need to finish work work at the entrance. It appears one sprinkler needs to be added outside of the entry way. Provide spare heads and head wrench. Provide rest of ceiling tile in the framing room. Provide additional hydraulic stickers for new remote areas at the riser. Verify that the existing backflow does or does not need to be forward flushed to verify the new/higher flow rate of the storage area.
|
INSP-Final Inspection | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | PART |
Troy Cobbley
|
|
|
Could not give final with no ceiling. Piping in and around the new framing room is ok to cover
|
INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 | P | FAIL |
Forrest France
|
|
|
Approved resubmitted plans are not available for inspection or verification of compliance.
|
INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 | P | PART |
Troy Cobbley
|
|
|
Deficiencies for the 6" tie in have been corrected.
|
INSP-Sprinkler Rough-in | 10/12/2005 | 10/13/2005 | 10/13/2005 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the 6" main. Need to fire caulk around the penatration to the fire riser room, provide additional clearance at thepenatrationthrough the CMU wall and provide a 4 way brace at the top of the 6" rise up piece in the future stock room.
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/10/2005 | 10/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
|
INSP-Final Inspection | 10/10/2005 | 10/10/2005 | 10/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
|