Permit Information
Permit NumberFIR05-00571
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11655 W MCMILLAN RD
Project NameSPR CROSS OF CHRI CHURCch
Customer Number 
ePlanReview 
Description
CROSS OF CHRIST EVANGELICAL LUTHERAN CHURCH * To install a complete overhead Light Hazard fire sprinkler system with underground service supply in a new 20,506-ft/2, one story masonry and wood framing addition (with a 3 hr fire wall separating the existing and new construction types) and the existing 6,010-ft/2 church building. A 5100-ft/2 portion of the masonry building addition will be framed with a future second floor, but will be unoccupied attic space. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-02937.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/13/20063/13/20063/13/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/10/20063/10/20063/10/2006AFAIL
DetailsTroy Cobbley
Sidewall sprinkler heads are still over spaced and all of the heads are still taped from the painters.
INSP-Sprinkler Rough-in/Hydro2/15/20062/15/20062/15/2006PFAIL
DetailsTroy Cobbley
Provide support for the two 2" vertical pipes and for the vertical drop to the FDC. The sidewall heads are over spaced from the center beams on both sides and the beam exceeds 8" which requires protection beneath. The above ground hydro test passed.
INSP-Final Inspection1/9/20061/9/20061/9/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanneman's permission for the church to occupy the new addition so that work can be completed in the existing area.
INSP-Sprinkler Rough-in/Hydro1/6/20061/6/20061/6/2006PPART
DetailsTroy Cobbley
Need to finish sprinkler expansion into the existing areas of the church. Per the structural inspector wall in two rooms will need to be extended to the deck. This may effect sprinkler coverage. I can find no record of a hydro test which will need to be done before the permit is finaled. Forward flush of the backflow preventor passed.
INSP-Final Inspection1/5/20061/5/20061/5/2006PCANC
DetailsTroy Cobbley
No inspection done due to lack of time but did notice water was turned off and tamper switches were not working
INSP-Sprinkler Rough-in12/7/200512/8/200512/8/2005APART
DetailsForrest France
Spacing in the narthex has been verified, seismic bracing has been modified as requested, an upright head in the nursery area is still blocked by ductwork as indicated on plans.
INSP-Sprinkler Rough-in11/16/200511/17/200511/18/2005APART
DetailsTroy Cobbley
Sprinkler piping is ok to cover except in the areas where deficiencies have been noted on the city approve plans. Resubmittals of the hydraulic calcs for area #3 are needed since upright heads exceed the 120 maz spacing allowed.
INSP-Sprinkler Rough-in/Hydro11/14/200511/15/200511/15/2005PCANC
DetailsTroy Cobbley
Need plans resubmitted and approved prior to calling in inspections.