INSP-Final Inspection | 2/13/2006 | 2/15/2006 | 2/15/2006 | A | PASS |
Forrest France
|
|
|
Items on correction notice have been completed, inspection passed.
|
INSP-Alarm Testing | 2/3/2006 | 2/3/2006 | 2/3/2006 | A | DEFR |
Forrest France
|
|
|
See c/n dated 2/2/06 for remaining issues.
|
INSP-Final Inspection | 1/31/2006 | 2/2/2006 | 2/3/2006 | P | FAIL |
Forrest France
|
|
|
The WON door on the 10th floor failed to function properly, batteries for the transponder panel for the 8th floor failed, one a/v in the short hall on 6th floor failed to operate, a/v devices at the restroom vestibules and select elevator lobbies have been relocated from location shown on approved plans (shown on as builts), one a/v on the 8th floor has been deleted in a vestibule that does not exist. Floors 5-11 core and common areas tested at this time.
|