Permit NumberFIR05-00596
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR UG ST AL'S FAMILY CNTR
Customer Number 
ePlanReview 
Description
St Al's Family Maternity Ctr - To install approximately 110' of C-900 CPVC underground with one 45 ell and one 90 ell and a yard PIV; and one MJ 90 ell and C-50 DI stub up through floor with 2" of insulation at collar. The inside riser cannot be located within the 2-hour rated stair enclosure. Per the architect for the TIN permit BLD05-01063, they will be submitting plans within the next couple of days, showing the riser to be separated from the stairwell with a 1-hour rated enclosure having an exterior door. This approval for the underground stub up location is contingent upon receipt and approval of those plans. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002, AWWA, the IFC-2003. No written review comments; final approval subject to plan annotations and satisfactory inspection by PDS/Fire.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/16/20089/16/20089/16/2008APASS
DetailsTroy Cobbley
Permit finaled
INSP-Supply line flush3/31/20063/31/20063/31/2006PPASS
DetailsTroy Cobbley
underground flush passed
INSP-Sprinkler Rough-in/Hydro3/30/20063/30/20063/31/2006PPASS
DetailsTroy Cobbley
Underground hydro test passed.
INSP-Sprinkler Rough-in1/25/20061/26/20061/26/2006APASS
DetailsTroy Cobbley
Three lengths of 6" underground supply piping have been installed along the face of the building. They are ok for cover.
INSP-Supply line flush10/19/200510/19/200510/19/2005PPASS
DetailsTroy Cobbley
Inspection was for stub out cover not flush. Underground stub out passed but has changed from coming out the north side to coming out the northwest side