INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 | P | DONE |
Forrest France
|
|
|
Permit expired per conversation with contractor.
|
DOC - Permit Expired | | | 3/17/2010 | | DONE |
Tisha Gallop
|
|
|
permit expired per Forrest France
|
INSP-Final Inspection | 5/18/2009 | 5/18/2009 | 5/18/2009 | P | PART |
Forrest France
|
|
|
Activities indicate underground supply line flush has not been completed, permit cannot be finaled at this time.
|
INSP-Sprinkler Rough-in | 5/2/2006 | 5/2/2006 | 5/2/2006 | P | PART |
Forrest France
|
|
|
UG hydrostatic test passed inspection.
|
INSP-Sprinkler Rough-in | 2/8/2006 | 2/9/2006 | 2/9/2006 | A | PASS |
Troy Cobbley
|
|
|
underground tie in to the united water supply is ok to cover. The piping from united water is not the 6" as shown on the plans but is actually 4". This inspector could not verify the "dead man" used to secured the 6x4 reducer. Pictures were taken and shown to Bill Alexander of the assembly.
|
INSP-Sprinkler Rough-in | 1/17/2006 | 1/17/2006 | 1/17/2006 | P | PASS |
Troy Cobbley
|
|
|
underground supply piping is ok to cover
|
INSP-Sprinkler Rough-in | 11/2/2005 | 11/2/2005 | 11/2/2005 | P | PART |
Forrest France
|
|
|
Underground riser and 5' stub out only are acceptable to cover.
|
INSP-Sprinkler Rough-in | 10/31/2005 | 10/31/2005 | 10/31/2005 | P | CANC |
Troy Cobbley
|
|
|
Not ready yet per Sam.
|