Permit Information
Permit NumberFIR05-00600
StatusExpired
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2291 N 15TH ST
Project NameSPR UG VILLA HIGHLANDS
Customer Number 
ePlanReview 
Description
Villa Highlands - To install 6" sprinkler underground and stub up into Mech Room 125. Mech Room is to be 1-hour rated (walls and ceiling/floor above), with exterior door for direct outside access; to have inside sprinkler control valve. Underground to be approx 125' of C-900, with one 45 ell and one MJ 90 ell, C-50 DI stub up riser through floor with 2" pipe insulation. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002, AWWA, the IFC-2000. No written review comments; final approval subject to plan annotations and satisfactory inspection by PDS/Fire.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference3/16/20103/17/20103/17/2010PDONE
DetailsForrest France
Permit expired per conversation with contractor.
DOC - Permit Expired  3/17/2010 DONE
DetailsTisha Gallop
permit expired per Forrest France
INSP-Final Inspection5/18/20095/18/20095/18/2009PPART
DetailsForrest France
Activities indicate underground supply line flush has not been completed, permit cannot be finaled at this time.
INSP-Sprinkler Rough-in5/2/20065/2/20065/2/2006PPART
DetailsForrest France
UG hydrostatic test passed inspection.
INSP-Sprinkler Rough-in2/8/20062/9/20062/9/2006APASS
DetailsTroy Cobbley
underground tie in to the united water supply is ok to cover. The piping from united water is not the 6" as shown on the plans but is actually 4". This inspector could not verify the "dead man" used to secured the 6x4 reducer. Pictures were taken and shown to Bill Alexander of the assembly.
INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006PPASS
DetailsTroy Cobbley
underground supply piping is ok to cover
INSP-Sprinkler Rough-in11/2/200511/2/200511/2/2005PPART
DetailsForrest France
Underground riser and 5' stub out only are acceptable to cover.
INSP-Sprinkler Rough-in10/31/200510/31/200510/31/2005PCANC
DetailsTroy Cobbley
Not ready yet per Sam.