INSP-Final Inspection | 4/18/2006 | 4/18/2006 | 4/18/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
INSP-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 | A | PART |
Forrest France
|
|
|
Fire alarm for this permit is acceptable, corrections have been completed, final pending shell alarm finals wip.
|
INSP-Final Inspection | 11/29/2005 | 11/29/2005 | 11/29/2005 | P | DEFR |
Forrest France
|
|
|
Need updated plans showing added strobe, will verify supply air has been ducted to avoid mixing air in return at final inspection.
|
INSP-Final Inspection | 11/2/2005 | 11/4/2005 | 11/4/2005 | P | FAIL |
Forrest France
|
|
|
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
1) Need to add an additional strobe in reception area because of the column that blocks the 95 cd in the ceiling.
2) Duct detectors are installed in the return of the HP units, but the OSA is dumped into the return plenum, whereby the duct detector is actually monitoring "mixed" air.
|