Permit Information
Permit NumberFIR05-00620
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1445 W COMMERCE AVE
Project NameSPR HAYDEN BEVERAGE
Customer Number 
ePlanReview 
Description
(HAYDEN BEVERAGE-ADDITION) To install approximately 62' of 8" C-900 PVC from an existing 8" fire service supply, for the construction of a one story Type VB 47,307-ft/2 warehouse/office addition to existing 82,120-ft/2 unlimited area warehouse/office. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-0500775.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/2/20073/2/20073/2/2007PPASS
DetailsForrest France
UG supply line permit finaled, resubmitted and approved under FIR05-00659.
INSP-Final Inspection7/14/20067/14/20067/14/2006PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 7/14/2006 at 7:48:57 AM. Contact: ###-####.
INSP-Supply line flush2/21/20062/21/20062/21/2006PPART
DetailsForrest France
United Water on site to turn valve for UG fire supply line flushing, flush performed satisfactory.
INSP-Sprinkler Rough-in/Hydro1/19/20061/20/20061/20/2006AFAIL
DetailsForrest France
The actual UG field installation is entirely different from the submitted and approved plans. This project will require resubmittal of plans reflecting work as installed prior to inspection approval. NOTE: an in line tee has been cut in the existing supply for the new riser and service restored to the existing system without first flushing the UG.
INSP-Sprinkler Rough-in1/19/20061/19/20061/19/2006PNR
DetailsForrest France
Inspection to be completed on 1/20.