Permit Information
Permit NumberFIR05-00635
StatusFinaled
Name PROTEX
Site Address 3300 S VISTA AVE
Project Namealm - out building
Customer Number 
ePlanReview 
Description
This is the first of two permits to provide visual notification in the common/public areas at the Holiday Inn. The first permit will include the out building. A NAC panel will be installed in the main building at the same location of the FACP.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/26/20072/27/20072/27/2007APASS
DetailsForrest France
Per inspection completed 12/5/05, FA final inspection passed. Permit finaled.
INSP-Alarm Testing12/5/200512/5/200512/5/2005PPASS
DetailsForrest France
c/n items have been performed, fire alarm passed inspection.
INSP-Final Inspection10/25/200510/26/200510/26/2005AFAIL
DetailsTroy Cobbley
The resident rooms do not meet the minimum sound requirements and the a/vs in the entry ways exceed 15' from the walls. Entry ways may be considered rooms if Mary agrees but strobe candella is still lacking. Interconnection between new NAC and panel has been tested and passed. End of line voltage for both NAC circuits has been tested and passed. Sound levels in the common areas passed.