INSP-Final Inspection | 2/26/2007 | 2/27/2007 | 2/27/2007 | A | PASS |
Forrest France
|
|
|
Per inspection completed 12/5/05, FA final inspection passed. Permit finaled.
|
INSP-Alarm Testing | 12/5/2005 | 12/5/2005 | 12/5/2005 | P | PASS |
Forrest France
|
|
|
c/n items have been performed, fire alarm passed inspection.
|
INSP-Final Inspection | 10/25/2005 | 10/26/2005 | 10/26/2005 | A | FAIL |
Troy Cobbley
|
|
|
The resident rooms do not meet the minimum sound requirements and the a/vs in the entry ways exceed 15' from the walls. Entry ways may be considered rooms if Mary agrees but strobe candella is still lacking. Interconnection between new NAC and panel has been tested and passed. End of line voltage for both NAC circuits has been tested and passed. Sound levels in the common areas passed.
|