Permit Information
Permit NumberFIR05-00651
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 8633 W FRANKLIN RD
Project NameMichaels The Arts & Crafts Sto
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required manual fire alarm system includes fire sprinkler riser monitoring, HVAC shutdown, elevator recall, voluntary smoke detectors in the second floor office and notification throughout. Manual pull stations not required per IFC 907.2.7 exception.

The associated building permit (BLD05-00627) is to construct a 7650 square foot, one story, addition on the east end of the existing Franklin Towne Plaza IV building and related site improvements. This addition is for the expansion of the existing Michaels Arts & Crafts tenant space. This permit will also include the remodel of the Michaels tenant space to add a new 390 sq. ft. classroom space and a new office area at the northwest corner of the retail space and to add a new 800 sq. ft. framing room at the southwest area of the retail space. The addition was able to be done by vacating the Bird Street right-of-way and relocating the east property line. The entire Franklin Towne Plaza IV building is considered one building. The sprinkler system is used for area increase. The new building area with the addition is 51,750 square feet, first floor 38,690 sq. ft., second floor 13,060 sq. ft.. All construction per the approved plans and attached comment list. JCM - - 8/23/05 - - This permit is being modified to relocate the new office, cash room and classroom to the north wall of the new expansion at the east side of the building and to remove the two existing small entry vestibules and construct one new larger entry vestibule.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/2/20063/2/20063/2/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/17/20062/17/20062/17/2006PCANC
DetailsTroy Cobbley
Unable to get elevator contractor to site for adjustments
INSP-Final Inspection2/15/20062/17/20062/17/2006AFAIL
DetailsTroy Cobbley
Need to test the smoke detector at the top of the shaft and the flashing hat is not working
INSP-Final Inspection2/14/20062/16/20062/15/2006AFAIL
DetailsTroy Cobbley
Need to verify signals, test elevator recall. A smoke detector and horn/strobe on the second floor are overspaced. Need to test the a/v's in the checking cashing tenant and the massage parlor.
INSP-Final Inspection10/17/200510/18/200510/18/2005APART
DetailsTroy Cobbley
Fire alarm panel, duct smoke detectors in new area, one duct detector in existing area and a/v's in Micheals have been tested. No other items tested. The existing duct smoke detectors need proven that they function as installed or they will need relocated. New area of Micheals is ok to occupy with fire dept. permission.
INSP-Final Inspection10/17/200510/17/200510/17/2005PFAIL
DetailsTroy Cobbley
Tested the batteries and phone lines and one duct smoke detector in Michaels. Phone line programming had to be changed so it could be supervised and horns didn't work
INSP-Final Inspection10/14/200510/14/200510/14/2005PFAIL
DetailsForrest France
Request for temp. is denied.