Permit Information
Permit NumberFIR05-00660
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11655 W MCMILLAN RD
Project NameSPR UG CROSS OF CHRIST CHURCH
Customer Number 
ePlanReview 
Description
(CROSS OF CHRIST EVANGELICAL LUTHERAN CHURCH) To install approximately 325'-0" of 6" C-900 PVC underground fire service supply connected to a repair gate located in W. McMillan Rd. running south to approximately 6'-2" north of grid line 6 and up through the floor with a 6" stainless steel Ames "In-Building Riser" to approximately 6" above the proposed finished floor located in what is described as a "stairway" (reference review comments). This supply is for fire sprinkler protection in a new 20,506-ft/2 one story wood framed addition to an existing 6,010-ft/2 church building, separated with 3 hr fire wall. The entire new and existing building will be fully fire sprinklered for area. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. Overhead system was submitted under FIR05-00571. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-02937.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20061/5/20061/5/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Supply line flush11/14/200511/15/200511/15/2005APASS
DetailsTroy Cobbley
flush passed
INSP-Sprinkler Rough-in/Hydro11/14/200511/14/200511/14/2005PPART
DetailsTroy Cobbley
Hydro test was supposedly witnessed by the general contractor with Sam Rogers approval. I will need test papers with signatures for fire dept. Underground flush scheduled for tomorrow.
INSP-Supply line flush11/10/200511/10/200511/10/2005PCANC
DetailsTroy Cobbley
no time for inspection
INSP-Sprinkler Rough-in10/21/200510/21/200510/23/2005PPASS
DetailsTroy Cobbley
PIV valve installed. Stem still needs installed.
INSP-Sprinkler Rough-in10/13/200510/14/200510/14/2005AFAIL
DetailsForrest France
The yard post indicator as shown on approved plans is not installed, the north/south run and first thrust block are okay to cover.