Information based on query as of Wednesday, August 14, 2024.
Permit Information
Permit NumberFIR05-00664
StatusFinaled
Name MOUNTAIN ALARM
Site Address 2680 W HILL RD
Project Namealm - LDS CHURCH
Customer Number 
ePlanReview 
Description
To provide fire/smoke damper control (using total area smoke detection in the corridors basement and first floor) and HVAC shutdown to an existing local fire alarm system. A smoke detector over the FACP will be added with this permit.

The building permit BLD 05-01129 is to repave the existing parking lot of the main site (excluding side lots to east), remodel interior rooms on basement and main levels and replace existing mechanical system per approved plans. Work to include, selective demolition of interior partitions and finishes, construction of new partitions, relocation of kitchen area, construction of new accessible restroom, and installation of new ducted HVAC system throughout the building. Rmh (LDS CHURCH-REMODEL)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/13/20061/13/20061/13/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/12/20061/12/20061/12/2006PFAIL
DetailsTroy Cobbley
The duct detectors in the basement are mounted incorrectly. The fresh air must come in after the sampling tubes. Provide signage at the manual pull stations per IFC 907.4.4. Repair all exit signs and emergency lights. One smoke detector on the first floor needs relocated to be centered between the two diffusers.
INSP-Final Inspection1/9/20061/10/20061/10/2006PCANC
DetailsTroy Cobbley
Per the electrician the mechanical systems are dismantled and non functional at this point. No inspection performed.
INSP-Final Inspection1/5/20061/6/20061/6/2006PFAIL
DetailsTroy Cobbley
Alarm system was not ready to test. I did a walk through and found one location in the basement where the spot detector for the fire/smoke damper activation exceeded 5' from the damper. They are going to relocate it.