Permit Information
Permit NumberFIR05-00727
StatusFinaled
Name FIRE SERVICE OF IDAHO
Site Address 1520 N COLE RD
Project Name 
Customer Number 
ePlanReview 
Description
*Albertsons (Deli) #154
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/21/20109/22/20109/23/2010APASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection9/21/20109/21/20109/21/2010 PASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in7/12/20107/12/20107/12/2010PPASS
DetailsTroy Cobbley
permit finaled
INSP-Conference6/10/20107/1/20107/2/2010ADONE
DetailsTroy Cobbley
I left a message on Joan's voice mail at AIE ###-#### requesting job status.
INSP-Conference6/2/20106/10/20106/10/2010ADONE
DetailsTroy Cobbley
Per Joan the electrical work has been scheduled. She will call with a follow up status shortly.
INSP-Conference5/24/20106/2/20106/2/2010ADONE
DetailsTroy Cobbley
See todays entry for the final inspection for project status.
INSP-Final Inspection6/2/20106/2/20106/2/2010PFAIL
DetailsTroy Cobbley
When the system was tripped the appliances shut off but the lights under the hood did not shut off. Inspection was stopped. The hood suppression system did go to the fire alarm panel. I noted that the secondary phone line on the fire alarm panel was in a trouble condition. I notified Chad, the store manager that the phone line would need to be repaired as well as the lights shutting off under the hood. The manual pull station was not tested. No paper work was accepted. I also contacted Joan with AIE at ###-####.
INSP-Conference5/20/20105/24/20105/24/2010ADONE
DetailsTroy Cobbley
I spoke to Joan with AIE ###-#### and she was going to follow up with the installing contractor.
INSP-Conference5/12/20105/20/20105/20/2010ACANC
DetailsTroy Cobbley
Rescheduled for next monday.
FIR-Aging Inspection5/12/20105/12/20105/12/2010 NR
DetailsTroy Cobbley
Contractor is following up on the alarm interconnection. A follow up inspection has been scheduled for next week.
INSP-Final Inspection10/26/200511/8/200511/8/2005AFAIL
DetailsTroy Cobbley
No test was performed due to lights not turning off under the hood and the suppression system not being connected to the fire alarm system.