Permit Information
Permit NumberFIR05-00738
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 620 N 6TH ST
Project NameSPR ID EDUCATION ASSOCIATION
Customer Number 
ePlanReview 
Description
IDAHO EDUCATION ASSOCIATION * To install a complete underground fire service supply and overhead wet, grid, Light Hazard occupancy fire sprinkler system in an existing 15,690-ft/2 two-story building. The underground supply includes approximately 40'-0" of 6" C-900 PVC which offsets into a north east (unidentified) room of this building thought a wall with 6" approved ferrous pipe (not identified). Each floor consists of 7,845-ft/2. This building will be fully fire sprinklered under this permit. Fire sprinklers is for area and story to A-3 basic allowable increases, the allowance of non-rated exit corridors, the allowance for unenclosed exit stairways, and non-rated mechanical/boiler room. (The mechanical/boiler room, however, is a sprinklered incidental use area and is to be smoke tight construction with full height walls, self-closing smoke sealed doors, and smoke dampers at any duct penetrations). All fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-01295.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/5/20072/6/20072/5/2007APASS
DetailsTroy Cobbley
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in12/15/200612/15/200612/15/2006PPASS
DetailsForrest France
Previous c/n items have been completed, final inspection passed, permit okay to final.
INSP-Final Inspection12/12/200612/13/200612/14/2006AFAIL
DetailsForrest France
Missing automatic ball drip at the FDC, missing seismic bracing at the basement level 2.5" main as noted, escutcheons need to be installed at some locations.
INSP-Sprinkler Rough-in/Hydro6/1/20066/2/20066/2/2006APART
DetailsForrest France
UG hydrostatic test and overhead hydrostatic test for the two AG systems performed satisfactory.
INSP-Supply line flush5/31/20066/1/20066/2/2006PPART
DetailsForrest France
UG supply line flush performed satisfactory.
INSP-Sprinkler Rough-in12/22/200512/22/200512/22/2005PPART
DetailsForrest France
UG fire supply line is acceptable to cover.