DOC - Permit Finaled | | | 3/7/2006 | | |
|
|
|
supposed to use fir06-00141 for scope of work that was missed in this permit
|
INSP-Final Inspection | 1/27/2006 | 1/27/2006 | 1/27/2006 | A | PASS |
Forrest France
|
|
|
Overhead fire sprinkler work passed inspection, c/n items have been completed satisfactory.
|
INSP-Final Inspection | 1/19/2006 | 1/20/2006 | 1/20/2006 | A | PART |
Forrest France
|
|
|
CORRECTIONS REQUIRED:
1. The (existing riser) needs supported. (The weight of the riser is on the Wall P.I. penetrating through the frangible outside wall).
2. Elevator equipment room will require another sprinkler head. This head will need smoke detection located per NFPA 72-6.15.4.2. The detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinklers (so coordination must be required between the alarm and fire sprinkler contractors-verified by CM Company). (NFPA 72-6.15.4.1*)
|
INSP-Sprinkler Rough-in/Hydro | 1/6/2006 | 1/6/2006 | 1/6/2006 | P | PART |
Forrest France
|
|
|
Overhead rough-in is good for cover at the lobby, kitchen, corridor ,confrence and reception areas, two upright heads above drop ceiling at the market room need to be removed as indicated on plans, one upright head in the staff laundry is painted, need to verify enclosed space at the end of meeting room as marked on plans is noncombustible or sprinklered, rotate aux. drain for antifreeze system to the lowest portion of the pipe, provide flex coupling at the top of riser, need to complete seismic bracing.
|
INSP-Sprinkler Rough-in/Hydro | 12/20/2005 | 12/21/2005 | 12/21/2005 | A | PART |
Forrest France
|
|
|
Rough-in at vending, excersise, guest laundry, kitchen and corridor are acceptable to cover, two locations at service laundry are overspaced-see approved plans for locations.
|
INSP-Sprinkler Rough-in/Hydro | 12/12/2005 | 12/12/2005 | 12/12/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in at the hard lid area first floor lobby is approved for cover.
|
INSP-Sprinkler Rough-in | 3/7/2006 | 3/8/2006 | | P | |
|
|
|
Jeff ###-####
|