Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR05-00754
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - ST LUKES
Customer Number 
ePlanReview 
Description
To provide total notification, smoke detector and two (2) in-duct detectors for two (2) fire/smoke damper control in the new TI space located on the 7th floor. A new NAC panel will be added. Battery calculations appear to be sufficient. No written comments. The PDS Fire Inspector to field verify total visual coverage. Provide revised building map to PDS Fire Inspector with the architectural changes at time of inspection.

The associated building permit (BLD05-02323) is to remodel of approximately 95 sq. ft. area to create a new private office. Work includes selective demolition; construction of approximately 8 feet of interior non-combustible wall with new 3' x 7' access door; installation of new suspended ceiling in remodeled area with light fixtures and diffusers; to add new drinking fountains in lobby, all per approved plans to include red-lined notes and all attached plan review conditions. (drs) (ST LUKES-EAST WING-7TH FLR)(OFFICE AREA)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/21/200512/22/200512/22/2005APASS
DetailsForrest France
Defficient items have been corrected, inspection passed.
INSP-Final Inspection12/20/200512/21/200512/21/2005AFAIL
DetailsForrest France
Two dampers failed to close upon smoke detection, strobe in the new office is not in sync with the remainder of the floor strobes, discussed this situation with the contractor for pending remodel on this floor.