INSP-Final Inspection | 6/28/2006 | 6/29/2006 | 6/29/2006 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, final alarm inspection passed.
|
INSP-Final Inspection | 6/15/2006 | 6/16/2006 | 6/16/2006 | A | CANC |
Forrest France
|
|
|
Per phone call from contractor, inspection to be rescheduled due to jobsite conditions.
|
INSP-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 | A | FAIL |
Forrest France
|
|
|
Manual pull stations at several locations are installed above max. height allowed, one H/S is overspaced in the open office area, remote indicator for the duct detector in the computer room is non-functional, fire alarm wire at some locations is incorrectly attatched, need to test one duct detector above a confrence room. FACP, nac panel, batteries, phone lines tested okay. Still need to test a/v's, manual pulls, dB, verify signals, etc.
|