Permit Information
Permit NumberFIR05-00772
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6752 S BUSINESS WAY
Project NameSPR FEDEX DISTRIBUTION CENTER
Customer Number 
ePlanReview 
Description
FEDEX GROUND (PACKAGE DISTRIBUTION CENTER) - To install overhead and underground supply fire sprinkler protection work in a new 67,182-ft/2 one story, Type II-B, fully fire sprinklered, unlimited area building. The underground fire service supply is connected off the 10" C-900 loop in the west parking lot running approximately 55'-0" east to a location under the footing and up through the floor approximately 1'-0" above the finished floor, 13'-3" south of building grid #3 and 1'-0" from the inside wall. The overhead system is designed for OH-2 Occupancy with two 6" dry systems and a WPI control. All fire sprinkler system overhead and underground work shall comply with the IFC 2003, the attached review comments/conditions as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-03068.
July 12, 2006 - FEDEX DISTRIBUTION CENTER-OFFICES (PHASE 2) - Install light hazard overhead fire sprinkler protection in the offices located in the southwest corner of a new 67,182-ft/2 one story, Type II-B, fully fire sprinklered, unlimited area building. All fire sprinkler system overhead and underground work shall comply with the IFC 2003, the attached review comments/conditions as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell was also installed under this same permit. This permit is attached to building permit: BLD05-03068.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20072/5/20072/5/2007PPASS
DetailsForrest France
Items on previous correction notice have been verified for compliance, final fire sprinkler inspection passed, permit finaled.
INSP-Final Inspection2/1/20072/2/20072/2/2007ACANC
DetailsForrest France
Mike Bierman is the contact @ ###-####. Thank you Phone #: ###-####
INSP-Final Inspection1/31/20072/1/20071/31/2007AFAIL
DetailsForrest France
Need to adjust the tamper switch at the PIV, provide pendent heads in the head box, attatch "911" sign at the outside bell, dry system #2 exceeds allowable trip time per NFPA for the system size (water was delivered to the test connection at 1min. 30 sec.).
INSP-Sprinkler Rough-in/Hydro1/17/20071/18/20071/18/2007APART
DetailsForrest France
System 1 and 2 passed 24 hr. air test, pressure loss at system 2 was within the allowable 1 1/2 psi per NFPA 13.
INSP-Sprinkler Rough-in1/16/20071/17/20071/17/2007APART
DetailsForrest France
Begin 24 hr. air test at 10:00 am, start psi. at system 2 is 40.5, system 1 is 40 psi.
INSP-Sprinkler Rough-in/Hydro1/15/20071/16/20071/16/2007AFAIL
DetailsForrest France
Air test failed due to start pressures below the min. amount allowed per NFPA 13.
INSP-Sprinkler Rough-in/Hydro12/15/200612/18/200612/18/2006APART
DetailsForrest France
OH hydrostatic testing for the two dry systems and the single wet system passed. Also approved the rough-in installation for cover at the office area. Still need to perform 24 hr. air test on the dry systems per NFPA, noted missing flex couplings at the riser and provision for forward flow testing of the BFP.
INSP-Supply line flush12/13/200612/14/200612/14/2006APART
DetailsForrest France
UG fire supply line flush completed.
INSP-Supply line flush12/7/200612/8/200612/8/2006AFAIL
DetailsForrest France
Inspection for the UG fire supply line flush was not completed due to lack of sufficient water flow. Noted the yard PIV was not operating correctly and is installed below allowable 36" height above grade.
INSP-Sprinkler Rough-in/Hydro10/19/200610/20/200610/20/2006PPART
DetailsForrest France
UG fire supply line hydro test is satisfactory.
INSP-Sprinkler Rough-in10/18/200610/18/200610/18/2006PPART
DetailsForrest France
UG fire supply line is okay to cover, need as-builts reflecting yard PIV installation.
INSP-Sprinkler Rough-in6/15/20066/16/20066/16/2006APART
DetailsForrest France
UG fire supply line riser and stub-out appears satisfactory, no approved plans on site for verification of pipe size, etc., need to provide means for seismic clearance where the ductile riser will pass through floor slab, need to cover open ended MJ x flange adaptor at riser piece.