Permit NumberFIR05-00799
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1055 N CURTIS RD
Project NamealmSARMC-FAMILY MATERNITY CNTR
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system that includes required automatic detection, sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-01063) is to finish the exterior & interior of a 38,020 square foot, two story addition with mechanical penthouse, adjacent to and connected to the existing Labor & Delivery Unit by two connecting links; to create patient rooms, exam rooms, nursing stations, administrative support and Neonatal Intensive Care Unit on the second floor; installation of millwork, electrical, plumbing, mechanical, electrical, fire suppression, alarm and medical gas as per tenant needs and compliance with codes and ordinances; to install a suspended ceiling grid system and interior finishes; to remodel a portion of the existing FMC for sleeping rooms for medical personnel; and to install exterior glazing and finishes. (drs) (ST ALPHONSUS)(FAMILY MATERNITY CENTER EXPANSION/RENOVATION)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20071/22/20071/22/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/11/20071/11/20071/11/2007PFAIL
DetailsTroy Cobbley
All of the strobes are mounted too low. No testing performed.
INSP-Final Inspection9/15/20069/15/20069/15/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given until the phase II (remodeled existing area) is complete. The new FMC building is complete.
INSP-Alarm Testing9/13/20069/13/20069/13/2006AFAIL
DetailsTroy Cobbley
The a/v's need to be exchanged in the ICU area and the nomanclature needs to be changed at the riser room devices as discussed. All other items on the correction notice have been corrected.
INSP-Alarm Testing9/5/20069/6/20069/6/2006ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested today which included the induct detectors and duct detectors for unit shutdown. Per the mechanical contractor the max cfm in the trunk lines is roughly 1200. The simplex detectors are listed to 2000cfm.
INSP-Alarm Testing8/30/20068/31/20068/31/2006PDONE
DetailsTroy Cobbley
See city approved plans for locations of devices tested and problems found. This was only a partial test.
FIR-Aging Inspection6/28/20066/28/20066/29/2006 NR
DetailsTroy Cobbley
work is in progress