Permit Information
Permit NumberFIR05-00822
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 10175 W FAIRVIEW AVE
Project NameSPR INTERNET AUTO
Customer Number 
ePlanReview 
Description
(INTERNET AUTO) * To provide selective demolition, modification and installation of the existing system for the remodel and additions of an existing 36,600-ft/2 retail store with a 680-ft/2 mezzanine, to an automobile dealership, showroom, and repair garage and 1,200-ft/2 addition on the west side for a car wash area, and a 2,100-ft/2 second floor for the finance and general manager's office, per plans which may include red-lined notes, attached plan review conditions, regulated by the Fire Chief. This building is fully fire sprinklered for area increase. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00317.Original Scope of Work:
(INTERNET AUTO) * To provide selective demolition, modification and installation of the existing system for the remodel and additions of an existing 36,600-ft/2 retail store with a 680-ft/2 mezzanine, to an automobile dealership, showroom, and repair garage and 1,200-ft/2 addition on the west side for a car wash area, and a 2,100-ft/2 second floor for the finance and general manager's office, per plans which may include red-lined notes, attached plan review conditions, regulated by the Fire Chief. This building is fully fire sprinklered for area increase. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00317.
01/26/07 Modified Scope of Work As-Built:
These plans were modified to include additional sprinkler protection where required along a new demising wall, Showroom Entry and below the new mezzanine. The fire sprinkler riser was modified to include the addition of a 4" Back Flow Prevention device. A forward flow assembly was also installed. New calculations have been submitted to support the riser / supply modifications.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/29/20075/30/20075/30/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/24/20075/25/20075/25/2007ADEFR
DetailsForrest France
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
INSP-Final Inspection5/23/20075/24/20075/24/2007APART
DetailsForrest France
Per field inspection by M. Timmerman, need verification of the dry system capacity prior to final acceptance.
INSP-Sprinkler Rough-in/Hydro5/22/20075/23/20075/23/2007PPART
DetailsForrest France
Dry system air test passed within the allowable leakage amount, system lost 1/2 psi over 24 hrs.
INSP-Sprinkler Rough-in/Hydro5/22/20075/22/20075/22/2007PPASS
DetailsTroy Cobbley
The above ground and under ground hydro tests passed. The 24 hour air test was started at 1:30 with 43 psi showing on the guage.
INSP-Sprinkler Rough-in/Hydro5/16/20075/17/20075/17/2007AFAIL
DetailsTroy Cobbley
The overhead hydro was started but is now failed because the riser room door is locked and nobody seems to be able to find a key.
INSP-Sprinkler Rough-in/Hydro5/16/20075/16/20075/16/2007PDEFR
DetailsForrest France
Inspection rescheduled.
INSP-Sprinkler Rough-in5/1/20075/2/20075/2/2007APASS
DetailsTroy Cobbley
Items listed on the plans have been corrected.
INSP-Sprinkler Rough-in4/25/20074/25/20074/25/2007PPASS
DetailsTroy Cobbley
See the city approved plans for locations of inspection and for corrections required.
INSP-Sprinkler Rough-in4/23/20074/24/20074/24/2007AFAIL
DetailsTroy Cobbley
I was told I was not supposed to be in the building by who appears to be a flooring guy. No inspection performed
INSP-Sprinkler Rough-in2/13/20072/13/20072/13/2007PPASS
DetailsTroy Cobbley
See the city approved plans for the piping locations that are ok to cover
INSP-Conference1/5/20071/5/20071/5/2007PCANC
DetailsTroy Cobbley
Conference would have been for items that I dont inspect for
INSP-Sprinkler Rough-in12/6/200612/7/200612/7/2006APASS
DetailsTroy Cobbley
The sprinkler piping under the balcony is ok to cover
FIR-Aging Inspection5/1/20065/1/20065/2/2006 NR
DetailsTroy Cobbley
work in progess. resubmittals received last week