Permit Information
Permit NumberFIR05-00839
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1852 S CENTURY WAY
Project NameSPR GYM OUTFITTERS
Customer Number 
ePlanReview 
Description
GYM OUTFITTERS - To install a complete Ordinary Group 2 wet fire sprinkler system in a new 14,500-ft/2 one story Type V-B warehouse, assembly with showroom and offices building. Fire sprinklers are used for area. The underground is being installed under FIR05-00690. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-00632
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/14/20063/15/20063/15/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro2/27/20062/28/20062/28/2006APASS
DetailsTroy Cobbley
Above ground hydro test passed. The test was witnessed by the general contractor. Need to get copy of test papers.
INSP-Sprinkler Rough-in2/27/20062/28/20062/28/2006APART
DetailsTroy Cobbley
Need to provide one additional pipe hanger on the 1" armover over the north offices. Provide revised hydraulic calculations for 127sq. ft. sprinkler spacing. Provide certification for the backflow and forward flush. Provide tag for riser.
INSP-Sprinkler Rough-in/Hydro2/1/20062/1/20062/1/2006PPASS
DetailsTroy Cobbley
Underground hydro and flush passed