INSP-Final Inspection | 4/17/2006 | 4/18/2006 | 4/18/2006 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinkler permit finaled
|
INSP-Final Inspection | 4/13/2006 | 4/14/2006 | 4/14/2006 | A | FAIL |
Troy Cobbley
|
|
|
No city approved plans on site for inspection. The pendant head in the kitchen still exceeds 10' from the exterior wall. Pendant head in the upper bedroom exceeds 10' from wall. Light and ceiling fans are obstructing pendants in upper and lower bedrooms. Pendant head in den is blocked by arched entry into small connecting foyer (must be atleast 6' away). Need to pipe drain to exterior and provide correct orfice for testing. Underground has not been flushed yet. There may be other items that are addressed on the approved plans but was unable to verify due to missing plans.
|
INSP-Final Inspection | 4/12/2006 | 4/13/2006 | 4/14/2006 | P | CANC |
Troy Cobbley
|
|
|
Would it be possible to have this inspection around noon. James is the contact @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
INSP-Sprinkler Rough-in | 1/10/2006 | 1/11/2006 | 1/11/2006 | A | PART |
Forrest France
|
|
|
Overhead rough-in is acceptable to cover pending corrections as noted on plans including overspaced head at kitchen, overspaced head at 2nd floor hall, install head at master bathroom as indicated, the backflow device installed is not as submitted (provide correct device or verify calcs are the same), tenting at cold cavity areas is satisfactory.
|
INSP-Sprinkler Rough-in | 12/21/2005 | 12/22/2005 | 12/22/2005 | A | FAIL |
Troy Cobbley
|
|
|
Provide letter for installation prior to approved plans to bill, resubmit plans with piping changes. No inspection performed.
|