Permit Information
Permit NumberFIR05-00856
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 12785 W ASHCREEK ST
Project NameROLLING HILLS CHARTER SCHOOL
Customer Number 
ePlanReview 
Description
ROLLING HILLS CHARTER SCHOOL-UNIT "A" * To tie-in eight 2.5" connections with combine nine existing classroom bays of an existing 8,316-ft/2, prefabricated and relocated classroom and verify system design and installation. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02034
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/23/20065/24/20065/24/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/22/20065/23/20065/23/2006AFAIL
DetailsTroy Cobbley
Forward flush failed.
INSP-Conference5/17/20065/17/20065/17/2006PDONE
DetailsTroy Cobbley
Correction notice left with Carolyn Mauer that all FIR permits to be finaled by 5-23-2006 or the school will be shutdown. I called Ken at AEI, Brad at SimplexGrinnell and left a message for Randy at DeBest about their permits needing finaled. I also contacted Dave Hanniman about what is going on.
INSP-Final Inspection5/5/20065/5/20065/5/2006PFAIL
DetailsTroy Cobbley
Repair the PIV tamper switch, insulate the underground in the crawl space, lower the FDC and provide through bolts for the EQ bracing.
FIR-Aging Inspection3/16/20063/16/20063/20/2006 NR
DetailsTroy Cobbley
I spoke to Chris with SimplexGrinnell he is to follow up on status.