INSP-Final Inspection | 5/5/2006 | 5/8/2006 | 5/9/2006 | A | PASS |
Forrest France
|
|
|
Corrections have been verified, fire alarm permit passed inspection.
|
INSP-Final Inspection | 4/27/2006 | 5/4/2006 | 5/4/2006 | A | FAIL |
Forrest France
|
|
|
Need to provide smoke detection at the double doors for release of mag locks per NFPA 72 2002, audibility appears to be inadequate at some locations as discussed and noted on plan review documents. Damper smoke detection, pull stations, EOL, and visual notification tested okay.
|
INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 | A | PART |
Forrest France
|
|
|
Audio/visual and duct detection devices tested satisfactory for the vending/break room and the smoking break room only for a portion of this permit.
|