INSP-Final Inspection | 3/6/2007 | 3/7/2007 | 3/7/2007 | A | PASS |
Forrest France
|
|
|
Final fire alarm inspection passed, permit finaled.
|
FIR-Aging Inspection | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | DONE |
Forrest France
|
|
|
Final inspection scheduled.
|
INSP-Final Inspection | 7/12/2006 | 7/13/2006 | 7/13/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need print out of the signals sent and updated plans showing the additional tamper switches.
|
INSP-Final Inspection | 3/8/2006 | 3/10/2006 | 3/10/2006 | A | PART |
Forrest France
|
|
|
c/n items have been completed, all items tested except two AHU detectors which are not installed at this time, provide signage on the door to the FACP.
|
INSP-Final Inspection | 3/2/2006 | 3/6/2006 | 3/6/2006 | A | PART |
Forrest France
|
|
|
7 AHU duct smoke detectors tested okay, 2 AHU detectors are not installed at this time, a ceiling will be required at the riser/FACP room which will require relocation and testing of the SD at the panel, need to test flow switches at the main riser (contractor unable to flow water at this time), tamper switch at antifreeze system point #6 needs adjustment, need to test low air and the WPI tamper at south riser as contractor had not made preparation to do so, provide signage at the door to the FACP.
|