INSP-Final Inspection | 4/3/2006 | 4/4/2006 | 4/4/2006 | A | PASS |
Forrest France
|
|
|
Fire alarm issues have been corrected as required, permit finaled.
|
INSP-Final Inspection | 3/31/2006 | 4/3/2006 | 4/3/2006 | A | FAIL |
Troy Cobbley
|
|
|
Zones 2 and 6 are reported as troubles but should be supervisory since they are tamper switches.
|
INSP-Final Inspection | 3/30/2006 | 3/31/2006 | 3/31/2006 | P | FAIL |
Troy Cobbley
|
|
|
Phone line troubles and induct detectors did not report correctly. Need to reverify all zones.
|
INSP-Final Inspection | 3/27/2006 | 3/29/2006 | 3/29/2006 | P | FAIL |
Forrest France
|
|
|
Two in-duct detectors failed to function properly, horn in the charging room does not sound the temporal pattern required for fire alarm and conflicts with the temporal pattern of the horn in the office, need to provide NFPA 72 Inspection and Testing form, a copy of central station signal verification of items tested today including panel, sprinkler monitoring, detection and notification devices, alarms, supervisory, and troubles from 3:50 to 5:00 pm today to be available on site at next inspection for review.
|
INSP-Final Inspection | 3/23/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Forrest France
|
|
|
Two tamper switches at the main control valves are not functional, panel for the local haz mat alarm has no phone line, need to provide completed NFPA 72 inspection and testing form prior to final inspection, no further inspection done at this time.
|