Permit NumberFIR05-00901
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2601 N BOGUS BASIN RD
Project NameSPR HEALTHWISE
Customer Number 
ePlanReview 
Description
HEALTHWISE BUILDING ADDITION - To install a combination Light Hazard wet system and a Class 1 Manual Standpipe system (in the North Stair Well) for a new 16,754-ft/2, three story, Type II-A office building addition. This building is fully fire sprinklered for 1 hour substitution. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness for compliance verification of minimum code. This permit is attached to building permit: BLD05-02015.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/12/200610/13/200610/13/2006APASS
DetailsForrest France
Required corrections have been made, fire sprinkler permit finaled.
INSP-Final Inspection10/10/200610/11/200610/11/2006ACANC
DetailsTroy Cobbley
No time for inspection due to time constraints and micron plan review
INSP-Final Inspection10/9/200610/10/200610/10/2006AFAIL
DetailsTroy Cobbley
pendant heads in the first floor wormens room are too close. When this is corrected a final will be ok
INSP-Sprinkler Rough-in/Hydro8/17/20068/18/20068/18/2006APART
DetailsForrest France
Overhead hydrostatic test for the three new system zones passed.
INSP-Sprinkler Rough-in/Hydro8/15/20068/16/20068/16/2006AFAIL
DetailsForrest France
1st and 2nd floor hydrostatic tests failed due to start pressures well below 200 psi ( 1st floor @190, 2nd floor @160).
INSP-Sprinkler Rough-in/Hydro8/14/20068/15/20068/15/2006PDEFR
DetailsForrest France
No time to complete inspection today, not all floors are ready for hydro per phone call from contractor, to be rescheduled.
INSP-Sprinkler Rough-in/Hydro8/11/20068/14/20068/14/2006ACANC
DetailsForrest France
Leroy stated that this was a hydro but final. His # ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
INSP-Sprinkler Rough-in4/28/20065/1/20065/1/2006APART
DetailsTroy Cobbley
Sprinkler inspection was for main and branchline rough-in only. No piping in the stairwells between columns 1-2 and 10-11 has not been installed or inspected yet. Piping for the most part is ok. The deficiencies have been marked on the city approved plans. The deficiencies include missing retaining straps, overspaced earthquaking, on the first floor riser nipples feeding branchlines where the plans shown supplies from the crosses and on the third floor all of the pipe hangers are attached to the bottom of the open web steel trusses (need engineers approval)