Permit Information
Permit NumberFIR06-00005
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 12501 W EXPLORER DR
Project Namealm - BOISE RESARCH CENTER
Customer Number 
ePlanReview 
Description
To provide six (6) duct smoke detectors with remote test switches for HVAC shutdown in the new TI space (Suite 100) and connect them to the existing required sprinkler monitoring fire alarm system. The matrix indicates the signal shall be an alarm. No written comments. Battery calculations appear to be sufficient. Provide updated building map that includes initiating devices and the architectural changes to the PDS Fire Inspector at time of inspection.

The associated building permit (BLD05-03164) is to remodel an existing 5712 sq ft tenant space for new office tenant per approved plans on file. Work to include, removal of interior partitions to create larger open office, construction of new interior partitions, infill roll up exterior door opening, installation of new suspended ceiling system and related lighting, installation of a new roof top HVAC system and related ducting, relocation of an existing breakroom sink, miscellaneous related interior finishes, this building is fully fire sprinklerd. ANY alterations to the sprinkler system and fire alarm system WILL REQUIRE SEPARATE PERMITS. (rmh) *(Sakson & Taylor)*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20061/20/20061/20/2006APASS
DetailsForrest France
Duct smoke detectors functioned and reported properly, inspection passed.