Permit Information
Permit NumberFIR06-00023
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 12754 W LASALLE ST
Project Namealm - LASALLE BLDG
Customer Number 
ePlanReview 
Description
To provide a nine (9) duct smoke detectors with RTSs to RTU 2 through 10 for HVAC shutdown to an existing required sprinkler monitoring fire alarm system which HVAC shutdown. The calculations appear to be sufficient. No written comments, PDS Fire Inspector to field verify functionality of the new duct detectors. An updated building map shall be provided at time of inspection.

The associated building permit (BLD05-01529) is to construct interior tenant improvements within a 16,365 square foot building for a tenant who will occupy the entire building. The building shell was constructed under permit BLD04-00958. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, two shower rooms accessible to the disabled, an access floor system, suspended ceilings, and finishes. The work is required to comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (LASALLE OFFICE BUILDING) This building is fire sprinklered for area increase.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20062/28/20062/28/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/22/20062/24/20062/24/2006PFAIL
DetailsTroy Cobbley
Relocate duct smoke detector as marked on the plans and test, repair the hvac unit that did not operate and test and test the duct smoke detector in the server room.