Permit Information
Permit NumberFIR06-00037
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1000 S VISTA AVE
Project NameSPR REILLY'S CHURCH SUPPLY
Customer Number 
ePlanReview 
Description
(REILLY'S CHURCH SUPPLY - VISTA VILLAGE) This building is partially fire sprinklered. There is a fire permit for Demolition Permit under FIR06-00010 issued to the same contractor, attached to the same building permit which has not been inspected to date. This permit is for the remodel an existing 6,555-ft/2 tenant space (3,284-ft/2 1st story and 3,271-ft/2 basement) for a new retail sales tenant. The fire sprinkler work is for the installation of sprinkler protection on the first floor, modifications of the existing system related to the New Stairwell located in the southwest basement, constructed to the first floor, the replacement of existing uprights in the basement, the modification of interior nonbearing walls in the basement, the adding of protection for the infill area where the demolition of existing stairs and sprinklers was permitted. Future canopy remodel and fire sprinkler installation will be done under BLD04-02464. This fire sprinkler work is required to comply with the approved drawings, the plan review report, and all applicable codes. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-03176.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/23/20063/23/20063/23/2006PPASS
DetailsForrest France
Required corrections have been made, fire sprinkler permit finaled.
INSP-Final Inspection3/16/20063/17/20063/17/2006APART
DetailsForrest France
Verified forward flow, PIV tamper has been disconnected from outside water flow bell as discussed, final pending plan resubmittals as required.
INSP-Sprinkler Rough-in/Hydro2/28/20063/1/20063/1/2006AFAIL
DetailsForrest France
Heads are overspaced at location adjacent to office wall and sales floor (exceeding 130ft/2), related demo permit FIR06-00010 must be called in for final, per plan review notes a plan re-submittal is required-see items #1thru 5, perform forward flow test for the backflow preventer (note: system riser modification may be required), system alarm and supervision must be tested and approved prior to final for this sprinkler permit.
INSP-Sprinkler Rough-in/Hydro2/27/20062/28/20062/28/2006PPART
DetailsForrest France
Overhead hydrostatic test is satisfactory, rough-in inspection not completed due to failure of the contractor to provide approved plans, review comments, and inspection card on site as required under condition of the permit.