INSP-Final Inspection | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work is satisfactory, permit finaled.
|
INSP-Final Inspection | 4/7/2006 | 4/7/2006 | 4/7/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need ceiling tile installed
|
INSP-Final Inspection | 3/20/2006 | 3/21/2006 | 3/21/2006 | A | PART |
Forrest France
|
|
|
Overhead rough-in is acceptable for cover at the drop ceiling areas, final pending installation of ceiling tile and escutcheons.
|
INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 | A | FAIL |
Forrest France
|
|
|
Various locations are overspaced beyond the maximum design area/density of 148 ft2, overspaced locations are marked on approved plans, one room marked as "file room" shall be spaced for ordinary hazard.
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2006 | 2/22/2006 | 2/22/2006 | P | PART |
Forrest France
|
|
|
Overhead rough-in at the hard lid area adjacent to the elevator lobby is good for cover.
|