Permit Information
Permit NumberFIR06-00041
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1450 N KIMBALL ST
Project NameSPR PETERSON AUTOPLEX-BDY SHP
Customer Number 
ePlanReview 
Description
PETERSON AUTOPLEX - BODY SHOP - To install a complete overhead fire sprinkler system and, starting at the property line, the underground supply for a new 16,875-ft/2 one story II-B auto body shop which includes 1,609-ft/2 office area and a 1,104-ft/2 storage mezzanine. The fire sprinklers are required for "Area." The fire sprinkler work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-02381.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20066/2/20066/2/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/30/20065/31/20065/31/2006AFAIL
DetailsTroy Cobbley
Not ready for final. Rough-in passed still need riser items addressed.
INSP-Supply line flush5/9/20065/10/20065/10/2006APASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Final Inspection5/9/20065/9/20065/9/2006PFAIL
DetailsTroy Cobbley
Inspection was not for a final but was for an underground hydro test which passed. I had sam measure the amount of leakage which was about 12oz. 15oz was allowed.
INSP-Sprinkler Rough-in4/19/20064/20/20064/20/2006APASS
DetailsTroy Cobbley
Sprinkler piping is ok to cover over the hardlid areas.
INSP-Sprinkler Rough-in/Hydro2/24/20062/24/20062/24/2006PPASS
DetailsTroy Cobbley
Underground supply piping is ok to cover