Permit Information
Permit NumberFIR06-00083
StatusFinaled
Name MOUNTAIN ALARM
Site Address 8574 E FAIRVIEW AVE
Project Namealm -
Customer Number 
ePlanReview 
Description
To required monitoring for a new cooking hood to an existing sprinkler monitoring fire alarm system. Three points are being added, a tamper switch to zone 22 (existing zone for tamper switches), a new pressure switch to zone 24 and the kitchen hood monitoring will be on zone 23. No written comments. The cooking hood permit (FIR05-00889) was issued 1/19/2006. The PDS Fire Inspector to field verify functionality. Provide revised building map at time of inspection.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/10/20064/10/20064/10/2006PPASS
DetailsForrest France
Inspection completed in the AM as previously agreed, fire alarm functioned properly, inspection passed.
INSP-Final Inspection4/5/20064/6/20064/6/2006ACANC
DetailsTroy Cobbley
No time to complete this inspection today, to be rescheduled per agreement with contractor.
INSP-Final Inspection4/3/20064/3/20064/3/2006PNR
DetailsTroy Cobbley
low air pressure switch has not been setup. no items tested except hood which tested ok