Permit Information
Permit NumberFIR06-00101
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2970 W ELDER ST
Project NameSPR CAMBRIA SUITES
Customer Number 
ePlanReview 
Description
(CAMBRIA SUITES) - This building is required to have a NFPA 13 Fire Sprinkler system used for area increase. To install a complete, wet, 13 system and a Class 1 Wet Manual Standpipe system with residential occupancies, in a new 78,220-ft/2, four story, wood framed, 119 unit motel with approximately 14,730-ft/2 areas for meeting rooms, indoor swimming pool, indoor spa, lobby and commercial food kitchen. Also a 650-ft/2 covered porte cochere entry. Underground fire sprinkler service supply was permitted under FIR05-00883. This permit is attached to BLD05-02392.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20074/2/20074/3/2007PPASS
DetailsForrest France
Required corrections have been verified for compliance, final fire sprinkler inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro4/2/20074/2/20074/2/2007PCANC
DetailsForrest France
johnathan; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
INSP-Final Inspection3/29/20073/30/20073/30/2007PFAIL
DetailsForrest France
The remainder of building final sprinkler inspection walkthrough completed today, noted heads are overspaced in the linen storage rooms on 2nd and 3rd floors, heads in the electrical room on the 4th floor are overspaced, missing heads at two mechanical closets on the 4th and 3rd floors, need to remove tape covering one head in the pool room, missing ceiling tile at the 1st floor storage rooms.
INSP-Final Inspection3/27/20073/28/20073/28/2007AFAIL
DetailsForrest France
Missing heads in the building storage room, blocked pendent at the first floor east stair landing, missing escutcheons at several locations, painted head in the pool room, missing flex coulpings at the riser, wet head in the cooler at 33 deg. maintained, one head is overspaced at the ADA room, inspection concluded at the first floor due to the number of defficient items found.
INSP-Final Inspection3/21/20073/23/20073/23/2007AFAIL
DetailsForrest France
Project is not ready for final as several defficiencies were noted on the first floor including overspaced heads, blocked and obstructed heads, missing escutcheons, painted heads, wet head in a cooler maintainig a temp of 35 deg, missing heads, missing ceilings, missing "911 sign", etc. Need sprinkler alarm supervision test and forward flow prior to final. Remainder of the full building sprinkler final walkthrough and test postponed until necessary corrections are made and contractor is ready for final.
INSP-Sprinkler Rough-in/Hydro3/20/20073/21/20073/21/2007PPART
DetailsForrest France
Retest of the 1st floor hydrostatic OH passed inspection.
INSP-Sprinkler Rough-in/Hydro3/16/20073/16/20073/16/2007PFAIL
DetailsForrest France
OH hydrostatic test failed for the 3" manifold system due to pressure loss at the guage, the 4" manifold system hydro passed.
INSP-Sprinkler Rough-in/Hydro3/8/20073/9/20073/9/2007AFAIL
DetailsForrest France
Correction notice items from the previous inspection for the antifreeze system completed on 2/27/07 are not complete, also noted to contractor some items still in need of completion including OH floors 1-4 and UG supply hydro tests, missing heads in the gravity chute, and remaining OH inspections.
INSP-Sprinkler Rough-in/Hydro2/27/20072/27/20072/27/2007PFAIL
DetailsForrest France
Inspection for the antifreeze system hydrostatic test failed due to visual leakage at two locations, also the SW heads as installed under the exposed composite wood joist obstructed construction ceiling do not meet requirements of NFPA 13 8.4.2 (1).
INSP-Sprinkler Rough-in/Hydro2/23/20072/26/20072/26/2007PCANC
DetailsForrest France
Cancel inspection per phone call from contractor.
INSP-Sprinkler Rough-in8/18/20068/21/20068/21/2006PPART
DetailsForrest France
c/n items related to the 1st floor rough-in have been completed, 2nd floor guest rooms are okay to cover.
INSP-Sprinkler Rough-in8/15/20068/16/20068/16/2006PFAIL
DetailsForrest France
Inspection for 1st floor rough-in failed due to overspaced hanger at east entry, blocked upright heads above the pool area in the concealed combustible space, missing hangers at some locations, head in the linen room is overspaced, branch line at the electrical room extends through both sides, one area at the SE as indicated on plans is not completed for inspection at this time.
INSP-Sprinkler Rough-in7/10/20067/11/20067/11/2006APART
DetailsForrest France
OH rough-in inspection at floors 3 and 4 only are okay for cover as discussed, one head is overspaced at guest room east side 4th floor, end of line heads at some locations exceed upward lift allowed and will require restraint, noted hanger overspacing at certain locations on 1" branch lines, heads at some locations will require adjustment to meet ceiling height, noted thermal expansion at grid system on the 3rd floor.
INSP-Sprinkler Rough-in7/7/20067/10/20067/10/2006ANR
DetailsForrest France
Per contractor the inspection request was intended for Tues. 7/11, no approved plans on site for review, to be rescheduled.