INSP-Final Inspection | 10/24/2006 | 10/24/2006 | 10/24/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm passed final inspection.
|
INSP-Alarm Testing | 10/20/2006 | 10/23/2006 | 10/23/2006 | P | CANC |
Forrest France
|
|
|
Inspection rescheduled due to time constraints.
|
INSP-Final Inspection | 7/26/2006 | 7/27/2006 | 7/27/2006 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given until the south tenant is complete
|
INSP-Final Inspection | 7/25/2006 | 7/25/2006 | 7/25/2006 | P | FAIL |
Troy Cobbley
|
|
|
Tamper switch on the riser #2 did not operate and the gas was not turned on for the hvac units for the testing of the duct smoke detectors. Signals should be redone since four alarm signals were sent but only three had been received at the monitoring agency.
|
FIR-Aging Inspection | 5/30/2006 | 5/30/2006 | 6/1/2006 | | NR |
Troy Cobbley
|
|
|
work in progress
|