Permit NumberFIR06-00128
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 417 S 6TH ST
Project NameSPR ADA COUNTY JUSTICE CENTER
Customer Number 
ePlanReview 
Description
(ADA COUNTY JUSTICE CENTER) This building is to be fully fire sprinklered for area increase and exit corridor fire rating reduction. This permit is to install the 6" underground supply and two wet, overhead OH-2 and Light Hazard Occupancy systems in an existing 50,900 ft/2 building for a new office and storage tenant. The entire basement consisting of 25,500-ft/2 will be sprinklered. The first floor also requires full fire sprinkler protection. Area reduction protection reduction has been requested to sprinkler only 18,080-ft/2 with 7,320-ft/2 of the 1st floor to be unprotected between grid lines "A" thru "F" and "1" thru "7". This building is to be fully fire sprinklered, until an approved agreement is on record/file with the Fire Department. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. Site work including parking was permitted under permit BLD05-02914. Interior demolition was done under permit BLD05-03470. This fire sprinkler scope of work is attached to BLD05-03413.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/30/20066/30/20066/30/2006PPASS
DetailsForrest France
Final fire sprinkler inspection passed, required corrections have been made, permit finaled.
INSP-Final Inspection6/29/20066/29/20066/29/2006PFAIL
DetailsForrest France
Need to provide a pressure relief valve for the grid system in the basement per NFPA 13, provide head cages at the exposed upright heads under stairs, one room marked "closet B108" in the basement is missing sprinkler coverage, provide as-builts reflecting actual field install at the first floor lobby where drop ceilings have been deleted and wall layouts changed as previously requested, need to provide playpipe to enable accurate testing of forward flow through the FDC- see review comments. Inspection concluded at this time due to the number of correction items noted as final field inspection is not designed for punch list or quality control purposes on behalf of the contractor.
INSP-Final Inspection6/28/20066/28/20066/28/2006PFAIL
DetailsForrest France
PIV tamper is adjusted incorrectly, provide "911" sign at the outside bell, the automatic ball drip for the FDC will not function as installed, no other items inspected for final at this time.
INSP-Sprinkler Rough-in/Hydro6/23/20066/23/20066/23/2006PPART
DetailsForrest France
Overhead hydrostatic test of the basement system is satisfactory.
INSP-Sprinkler Rough-in/Hydro6/23/20066/23/20066/23/2006AFAIL
DetailsForrest France
Guage read below 200 psi. at the start of test.
INSP-Sprinkler Rough-in/Hydro6/21/20066/22/20066/22/2006ACANC
DetailsForrest France
200lb hydro Contact: Steve; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro6/21/20066/21/20066/22/2006PPART
DetailsForrest France
Overhead hydrostatic test for the first floor wet system passed, basement system not ready at this time.
INSP-Sprinkler Rough-in/Hydro6/20/20066/21/20066/21/2006ACANC
DetailsForrest France
200lb hydro Contact: Steve; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro6/19/20066/20/20066/20/2006ACANC
DetailsForrest France
200lb hydro UG Contact: Steve ; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Supply line flush6/16/20066/19/20066/20/2006PPART
DetailsForrest France
UG supply line flush performed satisfactory.
INSP-Sprinkler Rough-in/Hydro6/16/20066/19/20066/19/2006APART
DetailsForrest France
This inspection was performed on friday afternoon 6/16. Overhead rough-in is acceptable to cover at the drop ceiling areas on the 1st floor. Items needing addressed include one overspaced head in the linen room, one painted head in a restroom, one head blocked by a surface mounted light in the janitors closet, need to provide plans reflecting actual field installation at the lobby area where the drop ceilings were deleted in lieu of OTS. The resubmitted plans are still only issued in a PARTIAL status due to hydraulic calculations per note #3-revise and resubmit for final approval.
INSP-Sprinkler Rough-in/Hydro5/24/20065/25/20065/25/2006AFAIL
DetailsForrest France
No inspection for cover at the drop ceiling areas performed as requested due to the "partial" approval status of the plans. Contractor to address items 1-3 on plan review notes prior to next field inspection.
INSP-Sprinkler Rough-in/Hydro5/23/20065/24/20065/24/2006PNR
DetailsForrest France
Not ready for inspection per phone call from contractor.
INSP-Sprinkler Rough-in/Hydro4/27/20064/28/20064/28/2006PPART
DetailsForrest France
Inspection for cover at the hard lid restrooms in the basement, noted one hanger ring to be changed at an arm over.
INSP-Sprinkler Rough-in/Hydro4/24/20064/25/20064/26/2006PPART
DetailsForrest France
Completed cover inspection for the 4" feed main inside wall through floor from basement to the 1st floor overhead system, okay to cover as marked on plans.
INSP-Sprinkler Rough-in/Hydro4/7/20064/10/20064/10/2006APART
DetailsForrest France
Overhead rough-in is good for cover at the four restrooms with hard lids on the first floor as marked on plans, no other areas requested for inspection at this time.
INSP-Sprinkler Rough-in/Hydro3/28/20063/29/20063/29/2006APART
DetailsForrest France
UG fire supply line is good for cover, the target window on the post indicator shall be aligned parallel to the underground pipe per review notes and requirements of IFC 2003.