Permit Information
Permit NumberFIR06-00146
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 1666 S ENTERTAINMENT AVE
Project NameSPR OH FUDDRUCKERS RESTAURANT
Customer Number 
ePlanReview 
Description
(FUDDRUCKERS RESTAURANT) Fire sprinklers used for area. To construct a complete overhead fire sprinkler system in a new 7,841-ft/2, one story Type V-B restaurant. Protection will be light hazard over the patio dining and inside dining, and Ordinary Group 1 protection for the Kitchen. The underground fire service supply was installed under FIR06-00026. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-02489.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/26/20065/30/20065/30/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/25/20065/26/20065/26/2006AFAIL
DetailsForrest France
The DP in the east side cooler is blocked by a surface mounted fan cooling unit, one head in the east dining area directly in front of a heat diffuser needs to be intermediate temp. rating, missing escutcheon at kitchen hallway east exit, provide signage for antifreeze riser, provide 200 deg. ssu for the head box, still need to test sprinkler related alarms and tampers at the riser.
INSP-Sprinkler Rough-in/Hydro5/16/20065/17/20065/17/2006PPASS
DetailsTroy Cobbley
Sprinkler piping located above the layin ceilings is ok to be covered. The two additional heads in the concealed pockets have been installed.
INSP-Supply line flush5/16/20065/17/20065/17/2006PPASS
DetailsTroy Cobbley
Underground hydro test passed.
INSP-Sprinkler Rough-in/Hydro4/11/20064/11/20064/11/2006PPASS
DetailsTroy Cobbley
Need to provide additional upright sprinklers as discussed in the dormer pockets and the pocket found below the decking near the main entrance. Piping is ok to cover. These items can be verified at final.