Permit Information
Permit NumberFIR06-00168
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 9050 W OVERLAND RD
Project NameSPR UG ANDERSON BLACK EAGLE
Customer Number 
ePlanReview 
Description
Anderson Black Eagle - (Shell & Core Underground) - To install underground fire sprinkler service for a new 32,640-ft/2, two story office and retail shell and core building. Separate fire permit required for overhead shell and tenant improvements for occupancy. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-03105.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/8/200611/8/200611/8/2006PPASS
DetailsForrest France
UG fire supply line permit finaled.
INSP-Sprinkler Rough-in/Hydro10/30/200610/30/200610/30/2006PCANC
DetailsTroy Cobbley
todd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Patricia Smith
INSP-Sprinkler Rough-in9/13/20069/15/20069/15/2006ACANC
DetailsTroy Cobbley
Wrong inspection number called in. I spoke with Todd about having the correct permit number called in for the work being inspected.
INSP-Sprinkler Rough-in9/13/20069/13/20069/13/2006PCANC
DetailsTroy Cobbley
todd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro9/12/20069/12/20069/12/2006PPASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Supply line flush9/1/20069/5/20069/5/2006APASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in6/26/20066/27/20066/27/2006APASS
DetailsTroy Cobbley
Remaining underground supply piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro4/24/20064/25/20064/25/2006APART
DetailsTroy Cobbley
This was a partial inspection of the underground. The 6" supply piping from the riser to the first 45 elbow is ok to cover. Per Dave with DeBest the piping will be at 4'-6" below grade even though it is not now. The grade will need to be atleast 3" above the bottom of the tilt up wall that passes over the piping.
INSP-Sprinkler Rough-in/Hydro4/18/20064/19/20064/19/2006ACANC
DetailsTroy Cobbley
Contact: Dave - Would like UG cover inspection for around 11 -- 11:30 if possible.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley