INSP-Final Inspection | 11/21/2007 | 11/27/2007 | 11/27/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 10/29/2007 | 10/30/2007 | 10/30/2007 | A | FAIL |
Troy Cobbley
|
|
|
The duct detector in the conference room did not shut down the hvac unit. All other items are ok. A map for the facp and nfpa 72 forms will be needed at the next inspection.
|
INSP-Final Inspection | 8/30/2007 | 9/5/2007 | 9/5/2007 | A | FAIL |
Troy Cobbley
|
|
|
One of the new a/v's in the exam rooms did not function, the existing devices need to be mounted at the code compliant heights as per the city approved drawings and manometer test need to be performed on the duct smoke detectors as requested on the previous correction notice. The duct detector will need to be tested for functionality as well.
|
INSP-Final Inspection | 6/12/2007 | 6/14/2007 | 6/14/2007 | A | FAIL |
Troy Cobbley
|
|
|
there were no city review notes or approved data sheets. See the city approved plans for locations where a/v's need to be added in exam rooms and candellas changed to what is marked on the approved plans.. Also it appears that all of the new duct smoke detectors are improperly placed and the incorrect sample tubes utilized. A manometer test will be required. Only one detector was tested and that was just to make sure the detector shut the unit down imediately. The supervision of the NAC panels by the facp has been tested ok. All of the existing device locations are too low to meet code compliance which Bob was going to verify could remain. One existing device has not been changed out to a new device and is marked on the plans.
|
FIR-Aging Inspection | 8/11/2006 | 8/11/2006 | 8/11/2006 | | NR |
Troy Cobbley
|
|
|
Per Amy with CSHQA the work is still in progress and they are waiting for as-builts.
|