Permit Information
Permit NumberFIR06-00183
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 2537 W STATE ST
Project NameBrady Law Office
Customer Number 
ePlanReview 
Description
To provide four (4) duct smoke detectors for HVAC shutdown for the new tenant space on the second floor. The PDS Fire Inspector to field verify. No written comments. The battery calculations appear to be sufficient. Provide revised building maps to PDS Fire Inspector at inspection time.

The associated building permit (BLD 05-03067) is to build-out and finish a 5,240 sq.ft. area for use as professional offices with support areas per approved plans. Approved plans include all review agency notes made on plans and all attached review agency comments. Work includes construction of interior walls to create private offices, open office areas, reception, library, breakroom, conference room and 4 fully accessible restrooms; install suspended ceiling grid system, millwork, upgrade electrical, mechanical, plumbing and sprinkler systems. drs (BRADY LAW OFFICES)(ST MARY'S CROSSING-BLDG 1-2ND FLR)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/7/20064/10/20064/10/2006APASS
DetailsForrest France
Corrections have been made, modifications tested, signals verified, fire alarm inspection passed.
INSP-Alarm Testing4/7/20064/7/20064/7/2006PFAIL
DetailsTroy Cobbley
four supervisory signal were sent but per the monitoring agency only three had been received. Need to test the elevator lobby smoke since it was relocated from the deck to the new ceiling.