Permit Information
Permit NumberFIR06-00222
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3748 W QUAIL HOLLOW DR
Project NameSPR CSC HOMES LLC
Customer Number 
ePlanReview 
Description
CSC HOMES LLC * To install a (modified) life safety NFPA 13D system in a five bedroom, three and half bathroom 4,079-ft/2 (3,147-ft/2 first floor, 932-ft/2 second floor), and an attached 923-ft/2 three car garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-01622.CSC HOMES LLC * To install a (modified) life safety NFPA 13D system in a five bedroom, three and half bathroom 4,079-ft/2 (3,147-ft/2 first floor, 932-ft/2 second floor), and an attached 923-ft/2 three car garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-01622.
01/08/07 Areas of Concern and Field Verification Required Prior to Final Acceptance:
This review is based on the following information and requirements, derived from the plans and submittals provided by the designer for permitting:
The water meter must be connected directly to the United Water service main since designer does not include any piping from the main to the meter and water supply certificate from United Water does not indicated the test was taken at or through the water meter.
( 81’ of Poly pipe was added to the calculations 01-08-07)
The designer calculations incorporate a 1½” AMES 2000B and the plans show/address a 1¼” which means the 1½” will be required. Plans and calcs must correlate.
(The plans & calculations now conform. 1¼” AMES 2000B 01-08-07)
The designer does not integrate on the plan the complete installation requirements (listing) for exposed CPVC piped risers. The bulk of the requirements not addressed on the plan are referenced in Item #15 below. IFC Fire/Life Safety inspector shall verify installation code of CPVC riser in this dwelling.
(Noted 01-08-07)
Only 2’-0” lift is shown in the calcs from the water supply to the base of the riser. Anything more may require resubmittal verification of design.
(Confirmed by an IFC Fire/Life Safety inspector. 01-07-08)
The font size of the underground site detail is nearly unreadable that verification of calcs and plan design is impossible to verify. The length allowed for the 1½” Polybutylene from the “SRC” (water meter) to the copper transition under the floor is: 81’-0” (per calcs).
(The plans have been revised. 01-08-07)
02/01/07 Re-Submittal Comments:
This review is based on changes made during construction.
These changes under Revision #2 do not appear to adversely affect the operation of the system as it was designed and approved. These plans dated January of 2007, shall be considered the last revision under this permit. Any further modifications will result in a complete resubmittal.
Under revision 2, 5 heads were added outside the remote area. The back flow device was a 1.25” Watts model 007. The approved riser location has also been moved from the originally approved location under this revision.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/13/20074/16/20074/16/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/6/20072/7/20072/7/2007PFAIL
DetailsTroy Cobbley
Need to have the pendant within 12" of the riser and the piping under the floor is still not insulated.
INSP-Final Inspection1/16/20071/17/20071/17/2007PFAIL
DetailsTroy Cobbley
There are still alot of problems. To start with the resubmitted plans do not show all of the added heads. One head is missing in the dining area. Another head is too close to a ornamental wood piece above a door. Neither the fitter or I could dislodge the access panel to the crawl space to verify pipe size and insulation as previously marked. There was no head within 12" of the riser. The riser is too far from the wall. No supply pressure guage was installed. The test and drain was not ran to the exterior. Plans need to be resubmitted with all of the information provided. Underground flush passed.
INSP-Final Inspection1/11/20071/16/20071/16/2007PCANC
DetailsTroy Cobbley
Per contractor the project is not ready for a final inspection
INSP-Final Inspection12/22/200612/22/200612/22/2006PCANC
DetailsTroy Cobbley
Call Mike Beiman First before you head out. Merry Christmas Forrest - RK Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
INSP-Final Inspection12/15/200612/18/200612/18/2006PCANC
DetailsTroy Cobbley
Per fitter the job is not ready for inspection. I notified him per my previous inspection entry that resubmittals were going to be required and that the computer showed no record of that being done.
INSP-Sprinkler Rough-in/Hydro5/2/20065/2/20065/2/2006PPART
DetailsTroy Cobbley
Sprinkler piping is ok to cover. Tenting passed. The riser has not been installed yet. The 1 1/4" piping that passes under the floor has not been insulated yet. Upon review of the plan review notes many items had not been addressed by the contractor and are left for field inspector to verify. I made a phone call to Bill Alexander and went over the items and it was decided that a resubmittal will be required. Much of the items concern the supply from the street. Other items include the added heads due to lights. One additional head will be required under the stairs due to obstructions. I notified Scott with Shilo of all of these items.